Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 742kW prp ; 818kW standby
- Manufacturer: MITSUBISHI
- Model: S12A2 PTA2
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 12-V
- Bore and Stroke: 150 x 160 mm
- Displacement: 33,93 L
- Cooling System: Water
- Lube Oil Specifications: API CD or CF SAE 30 or SAE 40
- Compression Ratio: 15,3:1
- Fuel Consumption ESP: 220 l/h
- Fuel Consumption 100% PRP: 195 l/h
- Fuel Consumption 75 % PRP: 147 l/h
- Lube oil consumption with full load: 0,8
- Total oil capacity including tubes, filters 120 L
- Total coolant capacity: 215 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 212 mm
- Oil temperature sensor
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: S6L1D.D4
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-00 18"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Elastic Coupling
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Water Jacket Heater with single phase pump
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 520 ºC
- Exhaust Gas Flow: 194 m3/min
- Maximum allowed back pressure: 600 mm H2o
- Heat dissipated by exhaust pipe: 719,13 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 4380 m3/h
- Cooling Air Flow: 19 m3/s
- Alternator fan air flow: 1,42 m3/s
- - STARTING SYSTEM.
- Starting power: 7,5 x 2 kW
- Starting power: 10,2 x 2 CV
- Recommended battery: 300 Ah
- Auxiliary Voltage: 24 Vdc
- Starter current peak: 720 A
- Nominal starter current: 380 A
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 75 mm Hg
- Maximum return feed pump: 150 mm Hg
- - DIMENSIONS.
- Length: 4.140 mm
- Height: 2.053 mm
- Width: 1.816 mm
- Maximum shipping volume: 15,43 m3
- Weight with liquids in radiator and sump: 6.530 kg
Length (A)414162.99
Width (B)181.671.50
Height (C)205.380.83
Weight with fluids in radiator and crankcase
6530
14398.65