Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 956,6kW prp ; 1056,6kW standby
- Manufacturer: MTU
- Model: 16V2000G36F
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 16-V
- Bore and Stroke: 135 x 156 mm
- Displacement: 35,7 L
- Cooling System: Water
- Lube Oil Specifications: ACEA E4, E6, E7, E9
- Compression Ratio: 17,5
- Fuel Consumption ESP: 246,86 l/h
- Fuel Consumption 100% PRP: 223,26 l/h
- Fuel Consumption 75 % PRP: 167,44 l/h
- Fuel Consumption 50 % PRP: 115,70 l/h
- Fuel Consumption 25 % PRP: 63,66 l/h
- Lube oil consumption with full load: 0,8 % of fuel consumption
- Total oil capacity including tubes, filters 114 L
- Total coolant capacity: 150 L
- Governor Type Electrical
- Air Filter Type Dry
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: HCI634K
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-0 18''
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Water Jacket Heater with single phase pump
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 545 ºC
- Exhaust Gas Flow: 207 m3/min
- Maximum allowed back pressure: 50 mbar
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 4572 m3/h
- Cooling Air Flow: 24,37 m3/s
- Alternator fan air flow: 1,614 m3/s
- - STARTING SYSTEM.
- Starting power: 7,5 kW
- Starting power: 10,2 CV
- Recommended battery: 200 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- - DIMENSIONS.
- Length: 4.950 mm
- Height: 2.452 mm
- Width: 2.021 mm
- Maximum shipping volume: 24,53 m3
- Weight with liquids in radiator and sump: 8.280 kg
Length (A)00.00
Width (B)00.00
Height (C)245.296.54
Weight with fluids in radiator and crankcase
8280
18257.4